Motor Full-Load Current Calculator
Calculate Breaker, Contactor, Overload & Wiring Sizing
Motor Parameters
Calculation Summary
NEC / IEC References
- NEC 430.6: Use NEC Table FLA values for sizing
- NEC 430.22: Conductors at least 125% FLA
- NEC 430.32: Overload at most 125% FLA (SF=1.0) or SF x FLA
- NEC 430.52: Breaker standard 150% FLA, max 250%
- IEC 60947-4-1: Contactor AC-3 rated at least FLA
Cable Sizing (NEC 430.22)
MCA (125% FLA): —
Derating: None (40C)
Method: IEC 60364-5-52 Method C
Cu Cable Table PVC 70C
| mm2 | Amps | AWG |
|---|---|---|
| 1.5 | 15 | 16 |
| 2.5 | 21 | 14 |
| 4 | 28 | 12 |
| 6 | 36 | 10 |
| 10 | 50 | 8 |
| 16 | 66 | 6 |
| 25 | 84 | 4 |
| 35 | 104 | 2 |
| 50 | 125 | 1 |
| 70 | 160 | 2/0 |
| 95 | 194 | 3/0 |
| 120 | 225 | 4/0 |
| 150 | 260 | 300MCM |
| 185 | 297 | 350MCM |
| 240 | 346 | 500MCM |
| 300 | 400 | 600MCM |
IEC 60364-5-52 Method C PVC 70C single circuit
Cable Notes
- Sized by ampacity only. Verify voltage drop for runs over 30m
- Apply derating for ambient above 40C or grouped cables
- For VFD use shielded motor cable
- Confirm with NEC, IEC 60364, BS 7671
