Maximum Cable Length Calculator
Maximum Cable Length Calculator
IEC 60228 Class 2Find the longest power cable run you can use before voltage drop goes over your limit. This maximum cable length calculator takes the supply voltage, load current, allowed voltage drop, conductor material and size, and returns the maximum one-way distance in metres and feet for DC, single-phase AC and three-phase AC circuits.
If you already know the length and want to check the drop, use our Voltage Drop Calculator. This tool works the other way round: it starts from the drop you can accept and solves for the longest cable.
How long can a cable be?
The maximum length depends on voltage, current, conductor size and the voltage drop you allow. Three examples with copper at 20 °C and a 3% limit:
- 24 V DC, 5 A, 2.5 mm²: about 9.7 m one way
- 230 V single-phase, 16 A, 2.5 mm²: about 29 m one way
- 400 V three-phase, 32 A, 10 mm²: about 118 m one way (resistance-only estimate, see the limits below)
Low voltage is the limiting factor. A 3% drop is only 0.72 V on a 24 V supply but 6.9 V on 230 V, so control circuits run out of length far sooner than mains circuits.
How to use the maximum cable length calculator
- Pick the circuit type. Choose DC 2-Wire, 1-Phase AC or 3-Phase AC. The voltage field changes to match (24 V, 230 V or 400 V defaults).
- Set the supply voltage. For three-phase, enter the line-to-line voltage.
- Enter the load current in amps. For motors or solenoids, use the running current and check inrush separately.
- Set the maximum voltage drop in percent. 3% is a common design target. Many 24 V control circuits need less.
- Choose the material and wire size. Copper sizes run from 1.5 mm² to 300 mm². Aluminium starts at 10 mm².
- Enter the operating temperature. The default is 20 °C. Hot panels and cable trays need a higher value.
- Read the result. The large number is the maximum one-way distance from source to load. The cards below it show the allowed drop in volts, the voltage at the load and the temperature-corrected resistance.
The result is the one-way length. On DC and single-phase circuits the current flows out and back, so the loop is twice that distance. The calculator already accounts for this.
The formula behind the calculator
The calculator uses a resistance-only Ohm’s law model:
L = (V × drop% / 100) ÷ (F × I × R(T) / 1000)
| Symbol | Meaning |
|---|---|
| L | Maximum one-way cable length (m) |
| V | Supply voltage (V). Line-to-line for three-phase |
| drop% | Allowed voltage drop (%) |
| F | 2 for DC and single-phase (out and back), 1.732 (√3) for three-phase |
| I | Load current (A) |
| R(T) | Conductor resistance in Ω/km at operating temperature |
Resistance is corrected for temperature with R(T) = R20 × [1 + α × (T − 20)], where α is 0.00393 per °C for copper and 0.00403 per °C for aluminium.
Resistance values used
R20 is the maximum DC resistance at 20 °C for Class 2 stranded conductors in IEC 60228. The calculator uses the values from the 2004 edition. The current edition is IEC 60228:2023, so if you need to confirm values for a specification, check them against that edition. The values agree with published cable-maker tables for IEC 60228 Class 1 and 2 conductors. They are standard maximum values, not the impedance of any specific cable.
| Size | Copper R20 (Ω/km) | Aluminium R20 (Ω/km) |
|---|---|---|
| 1.5 mm² | 12.1 | n/a |
| 2.5 mm² | 7.41 | n/a |
| 4 mm² | 4.61 | n/a |
| 6 mm² | 3.08 | n/a |
| 10 mm² | 1.83 | 3.08 |
| 16 mm² | 1.15 | 1.91 |
| 25 mm² | 0.727 | 1.20 |
| 35 mm² | 0.524 | 0.868 |
| 50 mm² | 0.387 | 0.641 |
| 70 mm² | 0.268 | 0.443 |
The calculator also covers 95, 120, 150, 185, 240 and 300 mm². For the standard itself, see the IEC webstore entry for IEC 60228:2023.
Worked examples
Example 1: 24 V DC sensor supply
A 24 V DC supply feeds a 5 A load through 2.5 mm² copper. Allowed drop is 3%.
- Allowed drop: 24 × 0.03 = 0.72 V
- Maximum loop resistance: 0.72 ÷ 5 = 0.144 Ω
- Resistance of 2.5 mm² copper: 7.41 Ω/km = 0.00741 Ω/m
- Loop length: 0.144 ÷ 0.00741 = 19.4 m, so the one-way length is 9.7 m
If you accept 5% drop, the limit rises to 16.2 m. Moving up to 6 mm² gets you to 23.4 m at 3%.
Example 2: Hot cable on a 24 V circuit
A 10 A load on 2.5 mm² copper at 3% drop gives 4.86 m at 20 °C. At 70 °C the copper resistance rises by about 20%, and the limit falls to 4.06 m. In a hot enclosure, ignoring temperature gives you a cable that is too long.
Example 3: 400 V three-phase motor feeder (estimate only)
A 32 A load on a 400 V three-phase supply uses 10 mm² copper at 3% drop.
- At 20 °C: 118.3 m
- At 60 °C: 102.2 m
- Same circuit in aluminium (10 mm², 20 °C): 70.3 m
This is a resistance-only result. For a motor feeder, treat it as a first estimate and read the AC limits section below. Get the motor current from our Motor FLA calculator. If you only know the power, convert it with the kW to Amps calculator or the kVA to Amps calculator.
Maximum cable length tables (3% voltage drop)
All values are one-way metres at 20 °C, calculated with the same formula and resistance data as the calculator.
24 V DC, copper
| Current | 1.5 mm² | 2.5 mm² | 4 mm² | 6 mm² | 10 mm² | 16 mm² |
|---|---|---|---|---|---|---|
| 1 A | 29.8 | 48.6 | 78.1 | 116.9 | 196.7 | 313.0 |
| 2 A | 14.9 | 24.3 | 39.0 | 58.4 | 98.4 | 156.5 |
| 5 A | 6.0 | 9.7 | 15.6 | 23.4 | 39.3 | 62.6 |
| 10 A | 3.0 | 4.9 | 7.8 | 11.7 | 19.7 | 31.3 |
230 V single-phase AC, copper
| Current | 1.5 mm² | 2.5 mm² | 4 mm² | 6 mm² | 10 mm² | 16 mm² | 25 mm² |
|---|---|---|---|---|---|---|---|
| 10 A | 29 | 47 | 75 | 112 | 189 | 300 | 475 |
| 16 A | 18 | 29 | 47 | 70 | 118 | 188 | 297 |
| 20 A | 14 | 23 | 37 | 56 | 94 | 150 | 237 |
| 32 A | 9 | 15 | 23 | 35 | 59 | 94 | 148 |
400 V three-phase AC, copper
| Current | 1.5 mm² | 2.5 mm² | 4 mm² | 6 mm² | 10 mm² | 16 mm² | 25 mm² | 35 mm² |
|---|---|---|---|---|---|---|---|---|
| 10 A | 57 | 93 | 150 | 225 | 379 | 602 | 953 | 1,322 |
| 20 A | 29 | 47 | 75 | 112 | 189 | 301 | 476 | 661 |
| 32 A | 18 | 29 | 47 | 70 | 118 | 188 | 298 | 413 |
| 63 A | 9 | 15 | 24 | 36 | 60 | 96 | 151 | 210 |
400 V three-phase AC, aluminium
| Current | 10 mm² | 16 mm² | 25 mm² | 35 mm² | 50 mm² | 70 mm² |
|---|---|---|---|---|---|---|
| 32 A | 70 | 113 | 180 | 249 | 338 | 489 |
| 63 A | 36 | 58 | 92 | 127 | 172 | 248 |
| 100 A | 22 | 36 | 58 | 80 | 108 | 156 |
For 12 V circuits, halve the 24 V lengths at the same current. The Engineering ToolBox 12 V wire length chart uses a fixed 2% drop and shows the total wire length out and back, so do not compare its numbers directly with the one-way results on this page.
What voltage drop limit should you use?
- NEC (United States): informational notes to 210.19(A) and 215.2(A) recommend limiting voltage drop to 3% on a branch circuit or feeder and 5% total to the farthest outlet. These are recommendations, not enforceable code requirements, although a local authority or a project specification can make them binding. The code is published by NFPA as NFPA 70, the National Electrical Code (current edition: 2026).
- IEC and BS 7671 installations: limits are typically in the 3% to 5% range depending on the circuit type. Our IEC 60364 cable sizing calculator covers those rules.
- 24 V DC control circuits: use the device datasheet. Find the lowest supply voltage each PLC input, sensor, valve or relay still accepts, then work backwards. Under-voltage often shows up as unreliable inputs, so see PLC input not working if you are chasing a symptom.
- Motors: low voltage raises current and heat. Size for running current here, then check starting conditions separately.
Limits of this calculator
This calculator estimates the maximum one-way cable length from conductor resistance and your chosen voltage-drop limit. It applies temperature-corrected resistance. It does not calculate full AC impedance, motor starting voltage drop or cable ampacity. Use the result for preliminary planning, then verify the cable against the load, the installation conditions, manufacturer data and your local code.
AC circuits: resistance only
On AC circuits the real voltage drop also depends on cable reactance and the load’s power factor. A common approximation for a balanced three-phase circuit is:
ΔV ≈ √3 × I × L × (R cos φ + X sin φ)
with R and X per unit length. The calculator uses the R term only, as if the load were purely resistive. In practice:
- On small conductors and DC circuits, resistance dominates and the result is a close estimate.
- On large conductors, long runs or low power factor loads (such as motors), reactance adds to the drop and the true maximum length is shorter than shown.
- For motor feeders, do not treat the result as a complete design limit.
Other limits
- Steady current only. Motor starting current, solenoid inrush and VFD output effects are not modelled. See our VFD to motor wiring guide for long motor cable considerations.
- Voltage drop is not the whole sizing job. Passing a voltage-drop check does not establish ampacity, short-circuit withstand, protective device suitability or compliance with local installation rules. Check ampacity with the wire size calculator and breaker rules with the NEC wire size and breaker calculator.
- Class 2 values only. The results use IEC 60228 Class 2 resistance values. Flexible (Class 5) copper conductors have slightly higher maximum resistance in cable-maker tables, for example 7.98 Ω/km against 7.41 Ω/km for 2.5 mm². Expect roughly 4% to 9% shorter lengths with flexible cable in the 1.5 to 10 mm² range.
- AWG labels are approximate. The dropdown shows nearest AWG equivalents only. Use the mm² size for the calculation.
How to get more cable length
When the result is shorter than your route, try these in roughly this order:
- Increase the cross-section. Going from 2.5 mm² to 6 mm² gives about 2.4 times the length.
- Raise the voltage. For the same power, doubling voltage halves the current and quadruples the length at the same percentage drop. This is why long DC runs are often 48 V rather than 24 V.
- Move the power supply closer to the load. A small 24 V supply near the machine beats a thick cable from the main panel.
- Reduce the current. Relocate loads or split them across two cables.
- Use parallel conductors where the terminals allow it.
- Keep conductors cool. Avoid bundling and hot enclosures, and enter the real temperature in the calculator.
- Allow more drop only where the load tolerates it. Check the datasheet first.
Searching for network or fieldbus limits instead? Data cables are limited by signal quality, not voltage drop, so this tool does not apply. See Modbus RTU vs Modbus TCP and PLC communication errors.
Frequently asked questions
What is the maximum length of a cable?
There is no single value. For power cables the limit comes from voltage drop, so it depends on voltage, current, conductor size, material and temperature. Enter your own values in the calculator above.
How do I calculate the maximum cable length for voltage drop?
Multiply the supply voltage by the allowed drop percentage, then divide by the resistance per metre times the current and the circuit factor. The formula is shown above. For three-phase circuits, the factor is 1.732 instead of 2.
Is the result one-way or round trip?
One-way. It is the distance from the source to the load. The calculator already counts the return conductor on DC and single-phase circuits.
Does the calculator include reactance and power factor?
No. It is a resistance-only estimate. On large conductors, long AC runs and motor loads the real maximum length can be shorter.
What is the maximum cable length for a 24 V DC circuit?
At 5 A on 2.5 mm² copper with a 3% limit, about 9.7 m. At 1 A, about 48.6 m. See the 24 V table above.
What voltage drop is acceptable?
Design guidance is commonly 3% for a branch circuit and 5% overall, although the NEC lists these as recommendations. For 24 V controls, use the lowest voltage your device accepts.
Does temperature change the maximum length?
Yes. Copper resistance rises about 0.39% per °C. A copper cable at 70 °C can be around 16% shorter than the same cable at 20 °C.
Copper or aluminium: which gives more length?
Copper. At the same size, aluminium has higher resistance, so its maximum length is about 60% of copper under the same conditions.
Can I use this for DC solar or battery cables?
For a quick estimate, yes, using DC 2-Wire mode with your system voltage. Check the cable’s ampacity and the manufacturer’s guidance as well.
Related calculators and guides
- Voltage Drop Calculator: calculate the drop for a known length
- Wire Size Calculator (NEC): ampacity and AWG selection
- IEC 60364 Cable Sizing Calculator: metric cable sizing
- 3-Phase Power Calculator: kW, kVA and amps for three-phase loads
- Watts to Volts Calculator: DC and AC conversions
- Common Industrial Electrical Problems: symptoms of low voltage and loose connections
Sources and references
- IEC 60228:2023, Conductors of insulated cables (IEC webstore)
- NFPA 70: National Electrical Code (2026 edition)
- Engineering ToolBox: 12 V maximum wire length chart
Disclaimer: This calculator and article are for education and preliminary planning. Final cable selection must account for ampacity, short-circuit withstand, protective devices, installation conditions and your local electrical code, and should be verified by a qualified person.
“`